MSC.1/Circ.1271
GUIDELINES FOR THE APPROVAL OF HIGH-EXPANSION FOAM SYSTEMS USING INSIDE AIR FOR
THE PROTECTION OF MACHINERY SPACES AND CARGO PUMP-ROOMS
(4
June 2008)
1.
The Committee, at its eighty-fourth session (7 to 16 May 2008), having
considered the proposal by the Sub-Committee on Fire Protection, at its
fifty-second session, approved the Guidelines for the approval of
high-expansion foam using inside air for the protection of machinery spaces and
cargo pump-rooms, as set out in the annex.
2.
Member Governments are invited to apply the annexed Guidelines when approving
inside air foam systems for ships of which the building contract is placed on
or after 1 July 2009 and bring them to the attention of ship designers,
shipowners, equipment manufacturers, test laboratories and other parties
concerned.
Annex.
GUIDELINES FOR THE APPROVAL OF HIGH-EXPANSION FOAM SYSTEMS USING INSIDE AIF FOR
THE PROTECTION OF MACHINERY SPACES AND CARGO PUMP-ROOMS
These
Guidelines apply to fixed high-expansion foam systems using inside air for the
protection of machinery spaces in accordance with SOLAS regulation
II-2/10.4.1.1, and cargo pump-rooms in accordance with SOLAS regulation
II-2/10.9.1.2. These Guidelines do not apply to cargo pump-rooms of chemical tankers
carrying liquid cargoes referred to in SOLAS regulation II-2/1.6.2. Fixed
high-expansion foam fire-extinguishing systems using inside air should
demonstrate by test that they have the capability of extinguishing a variety of
fires, which may occur in a ship's engine-room. Systems complying with these
Guidelines are not subject to the criteria stated in chapter 6 of the
International Code for Fire Safety Systems (FSS Code).
2.1
Foam is the extinguishing medium produced when foam solution passes through a
foam generator and is mixed with air.
2.2
Foam solution is a solution of foam concentrate and water.
2.3
Foam concentrate is the liquid which, when mixed with water in the appropriate
concentration forms a foam solution.
2.4
Foam mixing rate is the percentage of foam concentrate mixed with water forming
the foam solution.
2.5
Foam generators are discharge devices or assemblies through which foam solution
is aerated to form foam that is discharged directly into the protected space, typically
consisting of a nozzle or set of nozzles and a casing. The casing is typically
made of perforated steel / stainless steel plates shaped into a box that
enclose the nozzle(s).
2.6
Inside air foam system is a fixed high-expansion foam fire-extinguishing system
with foam generators located inside the protected space and drawing air from
that space. A high-expansion foam system using inside air consists of both the
foam generators and the foam concentrate.
2.7
Nominal flow rate is the foam solution flow rate expressed in l/min.
2.8
Nominal application rate is the nominal flow rate per area expressed in l/min/m2.
2.9
Nominal foam expansion ratio is the ratio of the volume of foam to the volume
of foam solution from which it was made.
2.10
Nominal foam production is the volume of foam produced per time unit, i.e.,
nominal flow rate times nominal foam expansion ratio, expressed in m3/min.
2.11
Nominal filling rate is the ratio of nominal foam production to the area, i.e.,
expressed in m/min.
2.12
Nominal filling time is the ratio of the height of the protected space to the
nominal filling rate, i.e., expressed in minutes.
2.13
Design filling rate is the minimum filling used during the approval tests in
accordance with appendix 2.
3. Principal requirements
for the system
.1
the system should be capable of manual release. Automatic release of the system
should not be permitted unless appropriate operational measures or interlocks
are provided to prevent the local application system from interfering with the
effectiveness of the system;
.2
the system should be capable of fire extinction, and tested in accordance with
appendix 2 to these Guidelines;
.3
the foam concentrates should be tested in accordance with MSC/Circ.670;
.4
the foam generators should be successfully tested in accordance with appendixes
1 and 3 to these Guidelines; and
.5
onboard procedures should be established to require personnel re-entering the
protected space after a system discharge to wear breathing apparatus to protect
them from oxygen deficient air and products of combustion entrained in the foam
blanket.
3.2 Requirements for the
system:
.1
the system should be supplied by both main and emergency sources of power and
should be provided with an automatic change-over switch. The emergency power
supply should be provided from outside the protected machinery space;
.2
the system and its components should be suitably designed to withstand ambient
temperature changes, vibration, humidity, shock, clogging and corrosion
normally encountered in machinery spaces or cargo pump-rooms in ships, and
manufactured and tested to the satisfaction of the Administration in accordance
with the requirements given in appendix 1 to these Guidelines. Piping, fittings
and related components inside the protected spaces should be designed to
withstand 925C;
.3
system piping, components and pipe fittings in contact with the foam
concentrate should be compatible with the foam concentrate and be constructed
of corrosion resistant materials such as stainless steel, or equivalent. Other
system piping and foam generators should be galvanized steel or equivalent;
.4
means for testing the operation of the system and assuring the required
pressure and flow should be provided by pressure gauges at both inlets (water
and foam liquid supply) and at the outlet of the foam proportioner. A test
valve should be installed on the distribution piping downstream of the foam
proportioner, along with orifices which reflect the calculated pressure drop of
the system. All sections of piping should be provided with connections for
flushing, draining and purging with air;
.5
the quantity of foam concentrate available should be sufficient to produce a
volume of foam equal to at least five times the volume of the largest protected
space at the nominal expansion ratio, but in any case not less than enough for
30 min of full operation for the largest protected space;
.6
means should be provided for the crew to safely check the quantity of foam
concentrate and take periodic control samples for foam quality;
.7
operating instructions for the system should be displayed at each operating
position;
.8
spare parts should be provided in accordance with the manufacturer's
instruction;
.9
the design filling rate for the system should follow the results of the tests
to be conducted in accordance with appendix 2 to these Guidelines, and should
be adequate to completely fill the largest protected space in 10 min or less;
.10
if an internal combustion engine is used as a prime mover for the seawater pump
for the system, the fuel oil tank to the prime mover should contain sufficient
fuel to enable the pump to run on full load for at least 3 h and sufficient
reserves of fuel should be available outside the machinery space of category A
to enable the pump to be run on full load for an additional 15 h. If the fuel
tank serves other internal combustion engines simultaneously, the total fuel
tank capacity should be adequate for all connected engines;
.11
means should be provided for automatically giving audible and visual warning of
the release of the system. The alarms should operate for the length of time
needed to evacuate the space, but in no case less than 20 s;
.12
the arrangement of foam generators and piping in the protected space should not
interfere with access to the installed machinery for routine maintenance
activities;
.13
the system source of power supply, foam concentrate supply and means of
controlling the system should be readily accessible and simple to operate, and
should be arranged at positions outside the protected space not likely to be
cut off by a fire in the protected space;
.14
the arrangement of foam generators should in general be designed based on the
approval test results. The number of generators may be different, but the
minimum design filling rate determined during approval testing should be
provided by the system. A minimum of two generators should be installed in
every space containing combustion engines, boilers, purifiers, and similar
equipment. Small workshops and similar spaces may be covered with only one foam
generator;
.15
foam generators should be uniformly distributed under the uppermost ceiling in
the protected spaces including the engine casing. The number and location of
foam generators should be adequate to ensure all high risk areas are protected
in all parts and at all levels of the spaces. Extra foam generators may be
required in obstructed locations. The foam generators should be arranged with
at least 1 m free space in front of the foam outlets, unless tested with less
clearance. The generators should be located behind main structures, and above
and away from engines and boilers in positions where damage from an explosion
is unlikely;
.16
the piping system should be sized in accordance with a hydraulic calculation
technique* to ensure availability of flows and pressures
required for correct performance of the system; and
_____________
*
Where the Hazen-Williams method is used, the following values of the friction
factor C for different pipe types which may be considered should apply:
Pipe type C
Black or
galvanized mild steel 100
Copper or copper
alloys 150
Stainless
steel 150
.17
for spaces greater than 500 m3, the arrangement of the protected
spaces should be such that they may be ventilated as the space is being filled
with foam. Procedures should be provided to ensure that upper level dampers,
doors and other suitable openings are kept open in case of a fire.
.1
after installation, the pipes, valves, fittings and assembled systems should be
tested to the satisfaction of the Administration, including functional testing
of the power and control systems, water pumps, foam pumps, valves, remote and
local release stations and alarms. Flow at the required pressure should be
verified for each section using orifices fitted to the test line. In addition,
all distribution piping should be blown through with air to ensure that the
piping is free of obstructions; and
.2
functional tests of all foam proportioners or other foam mixing devices should
be carried out to confirm that the mixing ratio tolerance is within + 30 to -0%
of the nominal mixing ratio defined by the system approval. For foam proportioners using foam concentrates of Newtonian type with
kinematic viscosity equal to or less than 100 cSt at 0ºC and density equal
to or less than 1.1 kg/dm3,
this test can be performed with water instead of foam concentrate. Other
arrangements should be tested with the actual foam concentrate.
APPENDIX 1.
COMPONENT MANUFACTURING STANDARDS FOR INSIDE AIR FOAM SYSTEMS
1.
Foam generator nozzles for inside foam systems should be tested in accordance
with the following items stipulated in appendix A of MSC/Circ.1165:
3.1 Dimensions
3.4.1 Flow
constant: the value of the flow constant K should be determined by measuring
the flow at the maximum operational pressure, minimum operational pressure and
the middle operational pressure.
3.11.1 Stress
corrosion: a representative sample extracted from the generator may be used.
3.11.2 Sulphur
dioxide corrosion: visual inspection only may be carried out.
3.11.3 Salt
spray corrosion: the test may be carried out at NaCl concentration of 5%.
Paragraph 3.14.2 in appendix A of MSC/Circ.668 need not be applied.
3.15 Resistance
to heat: where the components are made of steel, this test need not be applied.
3.17 Impact
test: only, the nozzles need to be tested.
3.22 Clogging
test: where the diameter of the opening of the nozzle exceeds 1.5 mm, this test
need not be applied.
2. Foam generators should also be tested in accordance with the
following items stipulated in standard EN 13565-1:
.1 clause 4:
General construction requirements (4.1 - connections, 4.5 - corrosion
resistance of metal parts, 4.8 - heat and fire resistance);
.2 clause 5:
Discharge coefficients;
.3 clause 6:
Quality of foam (6.2 - High-expansion components); and
.4 clause 9:
Components for medium and high-expansion foam systems.
Foam
generators should also be able to withstand the effects of vibration without
deterioration of their performance characteristics when tested in accordance
with paragraph 4.16 of appendix A of MSC/Circ.1165. After the vibration test,
the generators should show no visible deterioration and should meet the
requirements of clauses 5 and 9 of standard EN13565-1.
Equivalent
alternative testing standards may be used as determined by the Administration.
APPENDIX 2.
FIRE TEST METHOD FOR INSIDE AIR FOAM SYSTEMS
The
test method is intended for evaluating the extinguishing performance of inside
air high-expansion foam fire-fighting systems. System approval should be based
on the nominal filling rate, water pressure and other conditions used during
the specified tests.
The
components to be tested should be supplied by the manufacturer together with
design and installation criteria, operational instructions, drawings and
technical data sufficient for the identification of the components.
This
test procedure enables the determination of design criteria and the
effectiveness of inside air high-expansion foam fire-extinguishing systems
against spray and pool fires, which are obstructed by a simulated engine.
3.2.1
Test enclosure
3.2.1.1 The tests should be performed
in a room having an ambient temperature of 20 5ºC at the start of each
test. Details of the test hall geometry, the ventilation conditions and
environmental conditions should be given in the fire test report.
The
fire-extinguishing tests of the system should be carried out using the
following test compartments:
.1 Test
compartment 1
The test should
be performed in a 100 m2 room with a 5 m ceiling height and
ventilation through a 2 m x 2 m door opening according to figure 2. The engine
mock-up should be designed according to figures 1 and 3. The door opening to
the test compartment may be covered during the test at the same rate as the
foam layer is building up in the compartment to avoid foam leakage through the
door opening.
.2 Test
compartment 2
The test should
be performed in a test compartment having a volume greater than 1,200 m3,
but not greater than 3,500 m3, and a ceiling height exceeding 7.5 m.
The ventilation of the test compartment should be achieved by a 2 m x 2 m door
opening at floor level (as in test compartment 1) combined with a 20 m2
total ventilation area, distributed in the ceiling and/or along the walls, just
below the ceiling. The foam generators should not be positioned near the
openings. The door opening to the test compartment may be covered during the
test at the same rate as the foam layer is building up in the compartment to
avoid foam leakage through the door opening.
3.2.2
Simulated engine
The
fire test should be performed in a test apparatus consisting of:
.1 a simulated
engine of size (width x length x height) 1 m x 3 m x 3 m constructed of sheet
steel with a nominal thickness of 5 mm. The simulated engine is fitted with two
steel tubes of 0.3 m in diameter and 3 m in length, which simulate exhaust
manifolds and a grating. At the top of the simulated engine a 3 m2
tray is arranged (see figures 1 and 3); and
.2 a floor plate
system of 4 m x 6 m and 0.5 m in height surrounding the simulated engine with a
tray (4 m2 in area), underneath (see figure 1).
3.2.3
Test programme
The
fire test should be carried out using the following fire scenarios:
.1 combination
of the following fire programmes (Test fuel: commercial fuel oil or light
diesel oil):
.1 low-pressure
spray on top of the simulated engine centred with nozzle angled upward at a 45
angle to strike a 12 to 15 mm diameter rod 1 m away; and
.2 fire in trays
under (4 m2) and on top (3 m2) of the simulated engine;
.2 high-pressure
horizontal spray fire on top of the simulated engine. (Test fuel: commercial
fuel oil or light diesel oil);
.3 low pressure
concealed horizontal spray fire on the side of the simulated engine with oil
spray nozzle positioned 0.1 m in from the end of the simulated engine and 0.1 m2
tray positioned 1.4 m in from the engine end at the inside of floor plate.
(Test fuel: commercial fuel oil or light diesel oil); and
.4 flowing fire
0.25 kg/s from top of mock-up (Test fuel: heptane).
|
Fire type |
Low pressure |
High pressure |
|
Spray
nozzle |
Wide spray
angle (120 to 125) full cone type |
Standard
angle (at 6 bar) full cone type |
|
Nominal oil
pressure |
8 bar |
150 bar |
|
Oil flow |
0.16 0.01
kg/s |
0.050
0.002 kg/s |
|
Oil
temperature |
20 5C |
20 5C |
|
Nominal
heat release rate |
5.8 0.6
MW |
1.8 0.2 MW |
3.2.4
Installation requirements for tests
3.2.4.1
Foam generators should not be installed above the simulated engine in such a
way that the foam flow directly hits the test fires. The generators should also
not be located near ventilation openings.
3.2.4.2
Foam generators should be installed at the uppermost level of the space. The
vertical distance between the generators and test ceiling and floor should be
recorded and reflected in the manufacturer's design manual.
3.2.4.3
The number and spacing of foam generators should be in accordance with the
manufacturer's system design and installation manual.
3.2.4.4
The inlet water supply pressure to the foam generators should be maintained
within the acceptable range determined in paragraph 3.2.5 below, throughout the
tests.
3.2.5
Foam generator test
Representative
foam generators should be tested according to appendix 3 to these Guidelines.
The results of the testing should be reflected in the manufacturer's design and
installation manual.
4.1.1
Combination fire (paragraph 3.2.3.1 above): the 4 m2 fire tray below
the engine mock-up should be filled with at least 50 mm fuel on a water base
with a freeboard of 150 10 mm. The 3 m2 fire tray on top of the
engine should be filled with at least 50 mm fuel on a water base with a
freeboard of 40 10 mm (this requires that the notch on the side of the 3 m2
fire tray is blocked off by an appropriate means, e.g., steel plate).
4.1.2
Low pressure concealed fire and 0.1 m2 tray fire (paragraph 3.2.3.3
above): the 0.1 m2 tray should be filled with at least 50 mm fuel on
a water base with a freeboard of 150 10 mm.
4.1.3
Flowing fire (paragraph 3.2.3.4 above): the 4 m2 fire tray below the
engine mock-up should be filled with a 50 mm water base and the 3 m2
fire tray on top of the engine mock-up should be filled with a 40 mm water
base. The fuel should be ignited when flowing down the side of the mock-up,
approximately 1 m below the notch. The pre-burn time should be measured from the
ignition of