MSC.1/Circ.1268
GUIDELINES FOR THE APPROVAL OF FIXED PRESSURE WATER-SPRAYING AND WATER-BASED
FIRE-EXTINGUISHING SYSTEMS FOR CABIN BALCONIES
(30
May 2008)
1.
The Committee, at its eighty-fourth session (7 to 16 May 2008), having
recognized the need for guidelines for the approval of fixed pressure
water-spraying and water-based fire-extinguishing systems for cabin balconies,
taking into account the amendments to SOLAS chapter II-2 and the FSS Code
adopted by resolutions MSC.216(82) and MSC.217(82), considered the proposal by
the Sub-Committee on Fire Protection at its fifty-second session (14 to 18
January 2008) and approved the Guidelines for the approval of fixed pressure
water-spraying and water-based fire-extinguishing systems for cabin balconies, set
out in the annex.
2.
Member Governments are invited to apply the annexed Guidelines when approving
fixed pressure water-spraying and water-based fire-extinguishing systems for
cabin balconies on passenger ships for systems to be installed on or after 1 July
2008 and bring them to the attention of ship designers, ship owners, equipment
manufacturers, test laboratories and other parties concerned.
Annex.
GUIDELINES FOR THE APPROVAL OF FIXED PRESSURE WATER-SPRAYING AND WATER-BASED
FIRE-EXTINGUISHING SYSTEMS FOR CABIN BALCONIES
1.1
Fixed pressure water-spraying fire-extinguishing systems, as required by SOLAS
regulation II-2/10.6.1.3, for the protection of cabin balconies where furniture
and furnishings other than those of restricted fire risk are used should be
shown by testing to have the capability of suppressing typical fires expected
in such areas, and preventing them from spreading to the adjacent cabins and to
other balconies. These Guidelines should be applied when approving fixed pressure
water-spraying and water-based fire-extinguishing systems for cabin balconies
on passenger ships to be installed on or after 1 July 2008.
1.2.1
Automatic system is a system with automatic nozzles. Each head should be
individually activated by heat from the fire before water will be discharged.
1.2.2
Manually released system is a pipework system with open nozzles, controlled by
section valves. When a section valve is opened, all of the connected nozzles
will discharge water simultaneously.
2. Principal requirements for the system
2.1
The system should either be automatic or capable of manual release from a
location remote from the protected area.
2.2
The system should be capable of fire suppression based on testing conducted in
accordance with the appendix to these Guidelines.
2.3
The system should be capable of fire suppression on open deck areas with
expected wind conditions while the vessel is underway. The fire test does not
require the use of actual wind velocities; instead, a nominal wind speed is
included to account for variables in balcony geometry and related issues.
Although the test ventilation conditions are intended to provide a safety
factor, it is recognized that in an actual fire, the master and crew are
expected to take appropriate actions to manoeuvre the ship to assist the
suppression system.
2.4
The system should be available for immediate use and capable of continuously
operating for at least 30 min.
2.5
The system and its components should be suitably designed to withstand ambient
temperature changes, vibration, humidity, shock, impact, clogging and corrosion
normally encountered on open deck areas. Open head nozzles should be tested in
accordance with appendix A of MSC/Circ.1165*. Automatic nozzles should
be tested in accordance with appendix 1 of resolution A.800(19)*.
________________
*
These IMO instruments have been amended by MSC/Circ.1269 and resolution
MSC.265(84), respectively.
2.6
The location, type and characteristics of the nozzles should be within the
limits tested, as referred to in the appendix. Nozzle positioning should take
into account obstructions to the spray of the fire-fighting system. Automatic
nozzles should have fast response characteristics as defined in ISO standard
6182-1:2004.
2.7
The piping system should be sized in accordance with a hydraulic calculation
technique such as the Hazen-Williams hydraulic calculation technique* and the
Darcy-Weisbach hydraulic calculation technique, to ensure availability of flows
and pressures required for correct performance of the system.
_______________
* Where the Hazen-Williams
Method is used, the following values of the friction factor "C" for
different pipe types which may be considered should apply:
Pipe type C factor
Black or
galvanized mild steel 100
Copper and copper
alloys 150
Stainless
steel 150
2.8
The minimum capacity and design of the supply system for a manually released
system should be based on the complete protection of the most hydraulically
demanding section. The minimum capacity and design of the supply system for an
automatic system should be based on the complete protection of the eight most
hydraulically remote balconies, but not to exceed 50 m2.
2.9
The water supply for cabin balcony systems may be fed from an independent
supply, or they may be fed from the supply to another water-based fire-fighting
system providing that adequate water quantity and pressure are available as
indicated below:
.1 Manually
released systems: The water supply should be capable of supplying the largest
balcony section and, if supplied by the sprinkler system, the capacity should
be adequate to supply eight adjacent cabins. If supplied by the fire main, the
system should be capable of supplying the largest balcony section plus the two
jets of water required by SOLAS regulations II-2/10.2.1.3 and II-2/10.2.1.6.
.2 Automatic
systems: The water supply should be capable of supplying the eight most
hydraulically demanding balconies, but not to exceed 50 m2. If
combined with the sprinkler system, the design area in total need not exceed
280 m2.
2.10
The system should be grouped into sections. A manually released section should
not serve cabin balconies on both sides of the ship, except that the same section
may serve balconies located on one side of the ship and balconies in the fore
or aft end of the ship.
2.11
The system section valves and operation controls should be located at easily
accessible positions outside the protected space, not likely to be cut off by a
fire in the cabin balconies.
2.12
A means for testing the operation of the system for assuring the required
pressure and flow should be provided.
2.13
Activation of any water supply pump should give a visual and audible alarm at a
continuously manned central control station or onboard safety centre.
2.14 Any parts of the system which may be subjected to freezing
temperatures in service should be suitably protected against freezing.
2.15
The system should be provided with a redundant means of pumping or otherwise
supplying the discharge nozzles. The capacity of the redundant means should be
sufficient to compensate for the loss of any single pump or supply source. The
system should be fitted with a permanent sea inlet and be capable of continuous
operation using seawater.
2.16
Operating instructions for the system should be displayed at each operating
position.
2.17
Spare parts and operating and maintenance instructions for the system should be
provided as recommended by the manufacturer.
2.18
Dry pipe systems should be arranged such that water will discharge from the
farthest sprinkler within 60 s of actuation of the sprinkler.
APPENDIX.
TEST METHOD FOR FIXED PRESSURE WATER-SPRAYING AND WATER-BASED
FIRE-EXTINGUISHING SYSTEMS FOR CABIN BALCONIES
1.1
This test method is intended for evaluating the effectiveness of fixed pressure
water-spraying and water-based fire-extinguishing systems for cabin balconies.
1.2
It was developed for ceiling or sidewall mounted nozzles located to protect
external cabin balconies that are open to the atmosphere with natural wind
conditions.
1.3
Systems for the protection of cabin balconies are intended for either automatic
or manual operation.
2.1
The nozzles and other system components should be supplied by the manufacturer
with design and installation criteria, operating instructions, drawings, and
technical data sufficient for the identification of the components.
2.2
Temperatures should be measured using plain K-type thermocouple wires not
exceeding 0.5 mm in diameter. The thermocouple beads should be shielded to
protect against direct water impingement.
2.3
Unless otherwise stated, the following tolerances should apply:
.1 Length 2% of value
.2 Pressure 3% of value
.3
Temperature 2% of value.
2.4
System water pressure should be measured by using suitable equipment. Total
water flow rates should be determined by a direct measurement or indirectly by
using the pressure data and k-factor of the nozzles.
2.5
Wind velocity should be measured by using suitable equipment.
2.6
The temperature and pressure measurements should be made continuously, at least
once in every two seconds throughout the tests.
2.7
The tests should simulate the conditions of an actual installed system
regarding objectives such as time delays between the activation of the system
and minimum system water pressure or water delivery. In addition, the use of a
pre-primed fire suppression enhancing additive, if applicable, should be taken
into account.
3.1.1
These tests are intended to evaluate the fire-suppression capabilities of
nozzles used for the protection of cabin balconies against external fires in
furniture and furnishings of other than restricted fire risk. The primary
objective of the test is to evaluate the ability of the system to prevent a
fire on a cabin balcony from spreading to the adjacent cabin and to other
balconies.
3.1.2
The tests also define the following design and installation criteria:
.1 the maximum
coverage (length and width) of a single nozzle; and
.2 the minimum
operating pressure.
3.2.1
Fire test compartment
3.2.1.1
These tests are intended to evaluate the nozzle's fire-suppression capabilities
against external fires on open cabin balconies. The tests may be conducted
inside a well ventilated test hall having a specified area of at least 100 m2,
a specified height of at least 5 m and adequate natural or forced ventilation
to ensure that there is no restriction in air supply to the test fires. The
fire test hall should have an ambient temperature of 20 5C at the start of
each test.
3.2.2
Apparatus
3.2.2.1
The fire tests should be conducted in a test apparatus consisting of a balcony
mock-up in accordance with figure 1. The balcony ceiling should be smooth to
allow an unobstructed flow of gases.
3.2.2.2
The mock-up should be constructed of nominally 12 mm thick non-combustible
wallboard panels. Plywood panels should be attached to the wall below the
ventilation channel opening, and on the back wall, covering at least 2 m
horizontally, starting from the fan side corner. The panels should be 2 m high
and 3 to 4 mm thick. The ignition time of the panel should not be more than 35
s and the flame spread time at 350 mm position should not be more than 100 s as
measured in accordance with the FTP Code. Prior to the test, the plywood panels
should be conditioned at 21 2.8º C and 50 10%
relative humidity for at least 72 h.
3.2.2.3
The dimensions of the balconies should be in accordance with figure 1, or may
be increased up to the maximum coverage area (length and width) to be protected
by one nozzle.
3.2.2.4
A fan should be attached to the balcony mock-up, as indicated in figure 1. The
fan should provide an average air velocity of 5 0.2 m/s measured as an
average over several locations. Typically, sufficient dimensions of the fan are
0.8 m in diameter with a power of 5.5 kW.
3.2.2.5
For ceiling nozzles, the velocity measurements should be done at nine
locations; at the nozzle and around it on a circle of 0.5 m radius (figure
3(a)). For sidewall nozzles, the measurement should be done in six locations,
at the nozzle and around it on a half-circle of 0.5 m radius (figure 3(b)). In
vertical direction, the measurement should be done in the middle of the wind
channel (25 cm from the ceiling). The intention is to distribute measurement
locations over the region where the wind affects the suppression medium flow.
3.2.3
Fire source
3.2.3.1
The fire source should consist of a wood crib, two simulated chairs and a table
mock-up.
3.2.3.2
Each chair should be fitted with two 0.5 m by 0.8 m by 0.1 m polyether
cushions. The cushions should be made of non-fire retardant polyether and they
should have a density of approximately 33 kg/m3. When tested
according to standard ISO 5660-1 (ASTM E-1354), the polyether foam should give
results as given in the table below. Prior to the test,
the cushions should be conditioned at 21 2.8ºC and 50 10% relative humidity
for at least 72 h.
The
frame of the chairs should be of steel nominally 2 mm thick consisting of
rectangular bottom and backrest frames constructed of steel angles, channels or
rectangular stock of at least 3 mm thickness. The frame dimensions should be
0.5 m x 0.8 m (figure 2). The seat and backrest cushions should be supported on
each frame by steel bars 20-30 mm wide x 0.80 m long located in the centre of
the frames and welded to the edges. Steel plates should not be used to support
the cushions. The assembled frames should be supported by four legs 500 mm in
height constructed of similar steel stock. The frames should be equipped with a
metal wire net to support the cushions, and the backrest should be tied in
place, to keep from falling over during the test. The backrest should be placed
on top of the seat cushion.
|
ISO 5660: Cone calorimeter test Test
conditions: Irradiance
35 kW/ m2 Horizontal
position Sample
thickness 50 mm No
frame retainer should be used Test
results Foam Time
to ignition (s)
2-6 3
min average HRR, q180 270 5 0 Minimum
heat of combustion (MJ/kg)
25 Total
heat release (MJ/ m2) 50 1 2 |
3.2.3.3
A table should be constructed of a similar steel stock as the chairs. The table
should have a 0.5 m by 0.5 m metal frame, supported by four legs, 520 mm in
height. A 0.5 m by 0.5 m table plate should be fitted into the frame, made of 2
mm thick steel.
3.2.3.4
The two chairs should be placed in the fan side corner of the balcony, in such
a way that the polyether foam is 0.1 m from the plywood panel, according to
figures 3 and 4, corners of the cushions touching. The table should be placed
in the corner, edges aligned with the ends of the chairs.
3.2.3.5
The wood crib should be dimensioned 0.3 m x 0.3 m x 0.15 m (high). The crib
should consist of four alternate layers of four trade size nominal 38 mm x 38
mm kiln-dried spruce or fir lumber 0.3 m long. The alternate layers of the
lumber should be placed at right angles to the adjacent layers. The individual
wood members in each layer should be evenly spaced along the length of the
previous layer of wood members and stapled together. After
the wood crib is assembled, it should be conditioned at a temperature of 50
5ºC for not less than 16 h. Following the conditioning, the moisture
content of the crib should be measured at various locations with a probe-type
moisture meter. The moisture content of the crib should not exceed 5% prior to
the fire test.
3.2.3.6
A square steel tray of area 0.1 m2 and height 0.1 m should be
located under the table, so that its corner is next to the point where chairs
touch. The wood crib should be supported directly over the tray, edges aligned
with the chair ends. The top of the wood crib should be 0.27 m above the floor
level (figure 4).
3.2.3.7
For ignition, the tray should be filled with 1 l of water and 250 ml of
commercial heptane.
3.2.4
Nozzle installation requirements
3.2.4.1
The tests with the given balcony dimensions are intended for a single nozzle
protection. The single nozzle has to be located symmetrically in the balcony,
at the centreline in the position recommended by the manufacturer's
installation instructions, vertically at least 0.4 m above the lower edge of
the wind channel. The two most conceivable locations are shown in figure 3.
3.2.4.2
If the nozzle is located closer to the fan side wall than at the centreline,
the protection width of the nozzle will be less than 3 m, i.e. twice the tested
distance between the nozzle and wall. If a larger than 3 m protection width is
aimed at, a wider balcony should be constructed for the test.
3.2.4.3
The nozzle should be connected to a suitable water supply and arranged to operate
at the minimum pressure specified by the manufacturer.
3.2.4.4
The tests should be repeated using two nozzle orientations, where applicable.
At first, the lowest discharge density should be directed towards the cabin
wall, and then, towards the fan side wall.
3.2.5
Instrumentation
3.2.5.1
Thermocouples should be installed at four locations; two on the front edge of
the balcony ceiling, one 1 m and the other 2 m from the fan side wall, one of
the back edge of the ceiling, 2 m from the fan side wall and one in the centre
of the side wall opposite the fan. Thermocouples should be installed 30 mm from
the ceiling.
3.2.5.2
System water pressure should be measured near the nozzle, and the system water
flow rate should be defined with suitable means for the system.
4.1.1
Two tests should be done for each type of nozzle. One test with wind, and one
without.
4.1.2
In the wind test, the fan should be started before ignition and operated
continuously during the test. The wind velocity should be measured when it has
levelled, before ignition as defined in paragraph 3.2.2.5.
4.1.3
Automatic nozzles should be tested with the fusible element removed.